How many smoke detectors per room?

Enter the room dimensions and see detector count and positions live on the floor plan — the same tested calculation as in the PlanWerke planner, to the parameters of DIN 14676. Free, no sign-up, entirely in your browser.

Room
Roof slope
Room type
Detector type
3 smoke detectors
126 m² ÷ 60 m²/detector = 2.1 → rounded up 3
5.6 m5.6 m0.9 m2.1 m4.3 mRM 1RM 2RM 314 m9 mAutomatic placement · D_H 5.7 m · wall clearance 0.5 m
detectors
3
detectors
coverage radius D_H
5.7 m
coverage radius D_H
per detector (DIN 14676)
60 m²
per detector (DIN 14676)
minimum wall clearance
0.5 m
minimum wall clearance
Open in the planner
Planning proposal to the parameters of DIN 14676 — a standards-oriented sizing aid, not engineering design. Beams, fixtures and irregular shapes may require additional detectors; review remains with the planner.
App tip

3DFire for iPhone & iPad

Fire-protection planning on the go: 3DFire is available as an app on the Apple App Store — for iPhone and iPad.

Download on the App Store
01

The calculation behind it

The formula

⌈ area ÷ m² per detector ⌉

The detector count is the room area divided by the coverage area per detector, rounded up. To the parameters of DIN 14676 that coverage is between 60 and 150 m² — depending on room size, ceiling height and roof slope; the calculator shows the applied value.

The geometry

D_H · wall clearance 0.5 m

Every point of the room must lie within the coverage radius D_H of a detector; a minimum clearance of 0.5 m applies to walls. Angled rooms therefore sometimes need more detectors than the area formula yields.

Special case: corridors

≤ 15 m spacing · ≤ 7.5 m to the end

Corridors up to 3 m wide follow additional spacing rules: at most 15 m between two detectors, at most 7.5 m from the corridor end to the nearest detector.

02

Questions about detector counts

How many smoke detectors do I need per room?

In living rooms of ordinary size one smoke alarm is usually enough: up to 80 m² of floor area, DIN 14676 assigns a coverage area of 80 m² per detector. Larger rooms are divided by area and rounded up — a 126 m² room with a 3.2 m ceiling needs 3 detectors, for example (126 ÷ 60 = 2.1, rounded up 3). Angled rooms can require additional detectors through the geometry check.

Where do the calculator's values come from?

The calculator uses the same tested computation as the PlanWerke planner: coverage area per detector to the parameters of DIN 14676 — depending on floor area, ceiling height and roof slope — plus the coverage radius D_H and 0.5 m minimum clearance to walls. The computation runs locally in your browser; no data is transmitted.

Does the calculation apply to corridors too?

Yes. Setting the room type to “corridor” applies the special rules for narrow corridors: at most 15 m between two detectors and at most 7.5 m from the corridor end to the nearest detector — in addition to the area rule.

Does the calculator replace engineering design?

No. The result is a standards-oriented sizing aid — a planning proposal for professional review. Beams, fixtures, ceiling coffers and irregular shapes can change the placement; planning responsibility remains with the engineer.

DIN 14676DIN VDE 0833-2Computed in the browserFree